McCabe Engineering double skinned underground tanks are designed and constructed in full accordance with European Standards. As well as the very latest welding machinery, shot-blasting and high quality coating systems are all expertly applied in-house.
Mig welded internally and arc welded externally, ensures high quality and maximum weld integrity, resulting in a higher finished product strength. This quality is consistent from one tank to the next.
All underground tanks are blast cleaned to Sa2.5 followed by coating with Endoprene solvent-free polyurethane to a minimum thickness of 800 microns. Epoxy or bitumen coatings can also be provided to suit national requirements or specific ground conditions and materials of backfill. All coatings, regardless of material type are checked prior to despatch.
If you require any further information please Contact Us or call on: 0872250748 or 0876294664